Totalizing Electronic Weighing Indicator Controller With CE Certificate
Product Details:
| Place of Origin: | China | 
| Brand Name: | Supmeter | 
| Certification: | CE | 
| Model Number: | BST106-B60(T) | 
Payment & Shipping Terms:
| Minimum Order Quantity: | 1pcs | 
|---|---|
| Price: | Negotiation | 
| Packaging Details: | 1pcs/box | 
| Delivery Time: | 1-20 working days | 
| Payment Terms: | T/T, Western Union | 
| Supply Ability: | 2000pcs/month | 
| Detail Information | |||
| Power Supply: | DC24V | DI: | 6 | 
|---|---|---|---|
| DO: | 5 | COM1: | RS232 | 
| COM2: | RS485 | ||
| Highlight: | electronic weight indicator,digital load controller | ||
Product Description
Electronic Weighing And Totalizing Indicator Controller With CE Certificate
Main Applications
- Weight Display, Setpoint DO Output, Manual Totalizing.
- Weight Signal AO/Digit Transmission.
- Weight Limit DO Alarm Mode.
- Weight Increment DO Output Mode.
- Weight Decrement DO Output Mode.
- Weight Section DO Output Mode.

Main Features
- EMC design with high anti-jam for industrial environment.
- DC24V power input with reverse polarity protection.
- 32-bit ARM CPU with 48MHz clock & high arithmetic speed.
- 6+8 Red LED digital tubes for English&digit display.
- 24-bit ∑-△ADC with internal resolution 1/1,000,000.
- High sampling frequency 400Hz.
- Special Anti-vibration Digital Filtering Algorithm for precise weighing, stable display and rapid response.
- Auto Zero Tracking.
- Load Calibration & Data Calibration.
- Definable AO/COM[Communication Port].
Technical Specifications
- Power Supply: DC24V±20%, Max. 5W.
- Loadcell Excitation Voltage/Current: DC9V/120mA.
- 4 Loadcells[350Ω] connectable.
- Weighing Signal Input Range: 0~22.5mV.
- 6 Normally Open Switch Inputs [DI].
- 5 Normally Open Relay Outputs [DO]: AC250V/DC24V, 1A.
- 1 Analog Signal Output [AO]: 4~20mA, 0.05%FS.
- COM1: RS232.
- COM2: RS485.
- Connect Host IPC[Modbus] & Remote Display.
- Outline Size [W×H×D]: 110 × 62 × 150 mm.
- Panel Cut-out Size [W×H]: 94 × 47 mm.
- Operating Temperature: -25℃~+45℃.
- Protection Level of Front Panel: IP65.
- Accuracy Grade: III.
- Verification Accuracy: 0.03%.
- Static Weighing Accuracy: 0.2%~0.5%.
Model Panel-mounting Operation Interface

Keypad Operation
If there is not any keypad operation in one minute and it’s not in the processes of ‘F2 System Calibration’ & ‘F6 Factory Adjustment’, the controller will return to ‘Main Display Interface’ automatically.
| Menu Operation | |
| Key Name | Description | 
| 【MENU】 | Enter Main Menu. Exit. | 
| 【ENT】 | Enter / Save / Alarm Acknowledge. | 
| 【◄】 | Cursor shifts left. Display the previous option. | 
| 【►】 | Cursor shifts left. Display the next option. | 
| 【▲】 | Display the next interface or option. Digit input: +1 ( 0~9 loop). | 
| 【▼】 | Display the previous interface or option. Digit input: -1 ( 0~9 loop). | 
| Quick Operation | |
| 【MENU】 【Ñ】 * | 
 | 
| 【◄】 (【SET】) | Setpoint parameters setting. | 
| 【◄】 【ZERO】 【→0←】 * | 
 | 
| 【▲】 【TARE】 【→T←】 * | 
 | 
| 【ENT】 【G/N】 | Gross Weight / Net Weight display switch. | 
*: Keep the key pressed for 2 seconds.
Model Panel-mounting Installation

 
     
        